Juno TH TILT NFC and downlink description

Are you looking for the Juno TH TINFC and downlink description?

📄 You can view the PDF above or download it here .

Below is an overview of NFC and downlink configuration options available for the JUNO TH sensors. Tables for cross-product modules (Senticom/Sentivisor) can be found in the Generic NFC and Downlink documentation. Further information on configuring sensor communication can be found in the respective generic LoRaWAN® or mioty® documentation, depending on the version. Instructions valid for versions listed below.

NFC Configuration Modules

Module Module Key Group Group ID Description
Sentiface 0x1XXX Timings 0x00 Defines parameters for measurements and transmission behavior
Sentiface 0x1XXX Alarms and limit values 0x01 Defines alarms and limit values, e.g. upper temperature limit and lower temperature limit
Sentiface 0x1XXX Settings for opening detection 0x02 Defines measurement thresholds for triggering the alarm for temperature and relative humidity
Sentiface 0x1XXX Settings for tilt detection 0x03 Defines the behavior of the acceleration sensor

Applicable Article Codes

Article Code Features
S-JUNO-LOEU-TH JUNO TH sensor, temperature and relative humidity with tilt detection and opening detection LoRaWAN®
S-JUNO-IX-LOEU-TH INDUSTRIAL TH sensor, temperature and relative humidity with tilt detection and opening detection LoRaWAN®
S-JUNO-MIOTY-TH JUNO TH sensor, temperature and relative humidity with tilt detection and mioty® opening detection
S-JUNO-IX-MIOTY-TH INDUSTRIAL JUNO TH sensor, temperature and relative humidity with tilt detection and mioty® opening detection

ℹ️ Tables for cross-product modules (Senticom/Sentivisor) can be found in the Generic NFC and Downlink documentation.
Further information on configuring sensor communication can be found in the respective generic LoRaWAN® or mioty® documentation, depending on the version.
Instructions valid for versions listed above.

SENTIFACE: GROUP TIMINGS 0x00

Property Property ID Key (NFC/BLE) Min Max Default Unit Module Key
MEASUREMENT PERIOD 0x00 period 1/5* 360 30 min 1111
Specifies the period in which the measured values are recorded. 5 minutes means that a measurement is always taken by the sensor after 5 minutes.
* 5: For version S-JUNO-LOEU-TH and S-JUNO-MIOTY-TH
* 1: For version S-JUNO-IX-LOEU-TH and S-JUNO-IX-MIOTY-TH
REGULAR TRANSMISSION INTERVAL 0x01 every 1 64 6 1111
Number of measurements performed up to transmission.

SENTIFACE: GROUP ALARM SETTINGS 0x01

Resource Resource ID Key (NFC/BLE) Min Max Factory setting Unit Module key
ALARM ACTIVE 0x00 aact 0 3 1 1111
Indicates which alarms are activated, whether for temperature or relative humidity:
• 0: Both alarms deactivated
• 1: Temperature alarm active
• 2: Rel. humidity alarm active
• 3: Both alarms active
TEMPERATURE DELTA 0x01 tdt 1 50 5 °C 1111
Specifies by how much the temperature must change in absolute terms compared to the last transmission for an ALARM transmission to be triggered. This transmission is carried out independently of the normal transmission interval.
TEMPERATURE UPPER LIMIT 0x02 tht 0 85 40 °C 1111
Specifies the upper absolute limit value at which an alarm is triggered.
TEMPERATURE LOWER LIMIT 0x03 tlt -25 75 0 °C 1111
Specifies the lower absolute limit value at which an alarm is triggered.
REL. HUMIDITY DELTA 0x04 hdt 1 80 20 %RH 1111
Specifies by how much the relative humidity must change in absolute terms compared to the last transmission for an ALARM- transmission to be triggered. This transmission is carried out independently of the normal transmission interval (0x05 and following were used here for sample versions).
REL. HUMIDITY UPPER LIMIT VALUE 0x05 hht 5 100 80 %RH 1111
Specifies the upper absolute limit value at which an alarm is triggered.
REL. HUMIDITY LOWER LIMIT VALUE 0x06 hlt 0 95 20 %RH 1111
Specifies the lower absolute limit value at which an alarm is triggered.
HYSTERESIS TEMPERATURE 0x07 thy 2 0 10 °C 1111
Determines the absolute hysteresis in °C for state changes. If the temperature falls below or exceeds a threshold value minus hysteresis, the system switches from a higher to a lower alarm status.
HYSTERESE REL. AIR FLUID 0x08 hhy 5 0 30 %RH 1111
Determines the absolute hysteresis in %RH for status changes. If the relative humidity falls below or exceeds a threshold value minus hysteresis, the system switches from a higher to a lower alarm status.

SENTIFACE: OPENING DETECTION GROUP 0x02

Property Property ID Key (NFC/BLE) Min Max Default Unit Module Key
OPENING COOLDOWN 0x00 acool 0 600 0 sec 1111
Specifies a period of time in which, after the triggering of an opening, further openings cannot be triggered (debounces the openings). The reference value is the last counted opening.
OPENING TIME ALARM 0x01 oaaf 5 2880 10 min 1111
Indicates how long the lid is open until an alarm is triggered.
OPENING MODE 0x02 opmo 0 8 1 1111
Describes which direction the sensor is facing when closed and which angles trigger opening detection. Face-up means the sensor lies flat looking at the ceiling. Settings:
• 0: off
• 1: Ultra low power. Fixed threshold 50°. Closed when face down.
• 2: Ultra low power. Fixed threshold 50°. Closed when face up.
• 3: Ultra low power. Fixed threshold 50°. Closed when sidewards.
• 4: Extended tilt sensing. Adjustable threshold. Closed when face down.
• 5: Extended tilt sensing. Adjustable threshold. Closed when face up.
• 6: Extended tilt sensing. Adjustable threshold. Closed when sidewards.
• 7: Extended tilt sampling. Adjustable threshold. Auto-calibration of closed alignment.
• 8: Closed when solenoid is applied.
• 9: Open when solenoid is applied.

SENTIFACE: ADVANCED INCLINATION SETTINGS GROUP 0x03

Property Property ID Key (NFC/BLE) Min Max Default Unit Module Key
SAMPLING PERIOD 0x00 tspe 2 600 2 s 1111
Specifies how often the acceleration sensor determines the angle. The higher the frequency, the higher the power consumption.
TRIGGER LEVEL 0x01 ttle 5 180 20 ° 1111
Specifies the angle from which an opening is counted or an alarm is triggered.
TRIGGER HYSTERIA 0x02 tthy 1 90 4 ° 1111
Hysteresis value for the opening angle.

Specifications subject to change without notice. All information provided without guarantee.