Febris TH and NFC and Downlink Description

Are you looking for the Febris TH and NFC and downlink description?

Here you will find the NFC and downlink description for the Febris TH

Febris TH NFC and downlink table

Here you will find the table for a clear visualisation:

🔽🔽

 


Timings & Alarms group


Name: Measuring period
Communication protocol: All
Description: Specifies the period in which the measured values are recorded. 10 minutes means that a measurement is always taken by the sensor after 10 minutes.
Key (NFC parameter): period
Module: Sentiface
Module key: 0x1111
Group: 0x00
Property ID: 0x00
Preset value: 5
Minimum adjustable value: 5
Maximum adjustable value: 60
Unit: min
read/write: rw
Module key: 1111


Name: Regular transmission interval
Communication protocol:
All
Description:
Number of measurements after the sensor still schedules an uplink despite the absence of an alarm condition. 
Module:
Sentiface
Module key:
0x1111
Group:
0x00
Property ID:
0x01
Preset value:
6
Minimum adjustable value:
1
Maximum adjustable value:
12
Unit:
Anzahl
read/write: 
rw
Module key:
1111


Name: Save and transfer values (Use feature only after consultation)
Communication protocol:
All
Description:
Specifies whether past measured values are also sent: (from Minor version 1.2)

  • 0: off
  • 1: on
Module: Sentiface

Module key: 0x1121
Group:
0x00
Property ID:
0x02
Preset value:
Use feature only after consultation
Minimum adjustable value:
Use feature only after consultation
Maximum adjustable value:
Use feature only after consultation
Unit:

read/write: 
rw
Module key:
1121


Name: Number of stored values (Use feature only after consultation)
Communication protocol: All
Description: Maximum number of past measured values that are sent with a transmission. The actual number depends on the technology (from Minor version 1.2)
Key (NFC parameter): pastnum
Module: Sentiface
Module key: 0x1121
Group: 0x00
Property ID: 0x02
Preset value: Use feature only after consultation
Minimum adjustable value: Use feature only after consultation
Maximum adjustable value: Use feature only after consultation
Unit: 
read/write: rw
Module key: 1121


Alarm Settings group


Name: Delta value
Communication protocol: All
Description: Specifies the absolute amount by which the CO2 value must change compared to the last transmission for an ALARM transmission to be triggered. This transmission is carried out independently of the normal transmission interval.
Key (NFC parameter): delta
Module: Sentiface
Module key: 0x1111
Group: 0x01
Property ID: 0x00
Preset value: 300
Minimum adjustable value: 100
Maximum adjustable value: 2000
Unit: ppm
read/write: rw
Module key: 1111


    Name: Threshold value for yellow alarm
    Communication protocol: All
    Description: Specifies the CO2 threshold in ppm that must be exceeded for the sensor to switch to the yellow state (yellow LED lights up).
    Key (NFC parameter): yellow
    Module: Sentiface
    Module key: 0x1111
    Group: 0x01
    Property ID: 0x01
    Preset value: 1000
    Minimum adjustable value: 500
    Maximum adjustable value: 3000
    Unit: ppm
    read/write: rw
    Module key: 1111


      Name: Threshold value for red alarm
      Communication protocol: All
      Description: Specifies the CO2 threshold in ppm that must be exceeded for the sensor to switch to the red state (red LED lights up).
      Key (NFC parameter): red
      Module: Sentiface
      Module key: 0x1111
      Group: 0x01
      Property ID: 0x02
      Preset value: 2000
      Minimum adjustable value: 500
      Maximum adjustable value: 3000
      Unit: ppm
      read/write: rw
      Module key: 1111


          Name: Hysterese
          Communication protocol: All
          Description: Determines the absolute hysteresis in ppm for state changes. If the CO2 concentration falls below a threshold value minus hysteresis, the system switches from a higher to a lower alarm status.
          Key (NFC parameter): hyst
          Module: Sentiface
          Module key: 0x1111
          Group: 0x01
          Property ID: 0x03
          Preset value: 100
          Minimum adjustable value: 0
          Maximum adjustable value: 300
          Unit: ppm
          read/write: rw
          Module key: 1111


          Alarm data source and humidity alarm group


          Name: Alarm data source
          Communication protocol: All
          Description: Source on which the alarm is triggered, e.g. CO2, temperature or relative humidity
          • 0: CO2 Sensor
          • 1: Rel. humidity sensor
          Key (NFC parameter): ads
          Module: Sentiface
          Group: 0x05
          Property ID: 0x00
          Preset value: 1
          Minimum adjustable value: 0
          Maximum adjustable value: 1
          Unit:
          read/write: rw
          Module key: 1111

          Name: Rel. humidity Delta
          Communication protocol: All
          Description: Specifies by how much the relative humidity value must change in absolute terms compared to the last transmission for an ALARM transmission to be triggered. This transmission
          is carried out independently of the normal transmission interval.
          Key (NFC parameter): hdt
          Module: Sentiface
          Group: 0x05
          Property ID: 0x01
          Preset value: 20
          Minimum adjustable value: 5
          Maximum adjustable value: 100
          Unit: %
          read/write: rw
          Module key: 1111


          Name: Rel. humidity yellow alarm
          Communication protocol: All
          Description: Specifies the relative humidity threshold in ppm that must be exceeded for the sensor to switch to the yellow state (yellow LED lights up).
          Key (NFC parameter): hyt
          Module: Sentiface
          Group: 0x05
          Property ID: 0x02
          Preset value: 60
          Minimum adjustable value: 10
          Maximum adjustable value: 100
          Unit: %
          read/write: rw

          Module key: 1111


          Name: Rel. humidity red alarm
          Communication protocol: All
          Description: Specifies the relative humidity threshold in ppm that must be exceeded for the sensor to switch to the red state (red LED lights up).
          Key (NFC parameter): hrt
          Module: Sentiface
          Group: 0x05
          Property ID: 0x03
          Preset value: 80
          Minimum adjustable value: 10
          Maximum adjustable value: 100
          Unit: %
          read/write: rw
          Module key: 1111


          Name: Rel. humidity Hysterese
          Communication protocol: All
          Description: Determines the absolute hysteresis in ppm for state changes. If the CO2 concentration falls below a threshold value minus hysteresis, the system switches from a higher to a lower alarm status.
          Key (NFC parameter): hlh
          Module: Sentiface
          Group: 0x05
          Property ID: 0x04
          Preset value: 5
          Minimum adjustable value: 0
          Maximum adjustable value: 300
          Unit: %
          read/write: rw
          Module key: 1111


          Documentation Links

          You can find the links for further documentation on Febris TH here: