You are looking for the NFC and downlink description for the Febris SCW?
Here you can find the NFC and downlink description for the Febris SCW
Here you will find the table for a clear presentation:
🔽🔽
Group Timings & Alarms
Name: Measuring period
Communication protocol: All
Description: Specifies the period in which the measured values are recorded. 10 minutes means that a measurement is always taken by the sensor after 10 minutes.
Key (NFC Parameter): period
Modul: Sentiface
Modulschlüssel: 0x1111
Group: 0x00
Property ID: 0x00
Preset value:
Minimum adjustable value: 1
Maximum adjustable value: 60
Unit: min
read/write: rw
Module key: 1111
Name: Regular transmission interval
Communication protocol: All
Description: Number of measurements after the sensor still schedules an uplink despite the absence of an alarm condition.
Modul: Sentiface
Module key: 0x1111
Group: 0x00
Property ID: 0x01
Preset value:
Minimum adjustable value: 1
Maximum adjustable value: 12
Unit: Quantity
read/write: rw
Module key: 1111
Name: Save and transfer values
Communication protocol: All
Description: Indicates whether past measured values are also sent: (from Minor version 1.2)
- 0: off
- 1: on
Modul: Sentiface
Modulschlüssel: 0x1121
Group: 0x00
Property ID: 0x02
Preset value:
Minimum adjustable value:
Maximum adjustable value:
Unit:
read/write: rw
Module key: 1121
Name: Number of stored values
Communication protocol: All
Description: Maximum number of past measured values that are sent with a transmission. The actual number depends on the technology (from Minor version 1.2)
Key (NFC Parameters): pastnum
Modul: Sentiface
Module key: 0x1121
Group: 0x00
Property ID: 0x03
Preset value:
Minimum adjustable value:
Maximum adjustable value:
Unit:
read/write: rw
Module key: 1121
Alarm settings group
Name: Delta value
Communication protocol: All
Description: Specifies the absolute amount by which the CO2 value must change compared to the last transmission for an ALARM transmission to be triggered. This transmission is carried out independently of the normal transmission interval.
Key (NFC Parameters): delta
Modul: Sentiface
Module key: 0x1111
Group: 0x01
Property ID: 0x00
Preset value:
Minimum adjustable value: 100
Maximum adjustable value: 2000
Unit: ppm
read/write: rw
Module key: 1111
Name: Threshold value for yellow alarm
Communication protocol: All
Description: Specifies the CO2 threshold in ppm that must be exceeded for the sensor to change to the yellow state (yellow LED lights up).
Key (NFC Parameters): yellow
Modul: Sentiface
Module key: 0x1111
Group: 0x01
Property ID: 0x01
Preset value:
Minimum adjustable value: 0
Maximum adjustable value: 1000
Unit: ppm
read/write: rw
Module key: 1111
Name: Threshold value for red alarm
Communication protocol: All
Description: Specifies the CO2 threshold in ppm that must be exceeded for the sensor to switch to the red state (red LED lights up).
Key (NFC Parameters): red
Modul: Sentiface
Module key: 0x1111
Group: 0x01
Property ID: 0x02
Preset value:
Minimum adjustable value: 500
Maximum adjustable value: 3000
Unit: ppm
read/write: rw
Module key: 1111
Name: Hysteresis
Communication protocol: All
Description: Determines the absolute hysteresis in ppm for status changes. If the CO2 concentration falls below a threshold value minus hysteresis, the system switches from a higher to a lower alarm status.
Key (NFC Parameters): hyst
Modul: Sentiface
Module key: 0x1111
Group: 0x01
Property ID: 0x03
Preset value:
Minimum adjustable value: 0
Maximum adjustable value: 300
Unit: ppm
read/write: rw
Module key: 1111
Group Alarm Data source and humidity alarm
Name: Alarm Data source
Communication protocol: All
Description: Source on which the alarm is triggered, e.g. CO2, temperature or relative humidity
- 0: CO2 Sensor
- 1: Rel. Humidity sensor
Key (NFC Parameters): ads
Modul: Sentiface
Group: 0x05
Property ID: 0x00
Preset value:
Minimum adjustable value: 0
Maximum adjustable value: 1
Unit:
read/write: rw
Module key: 1111
Name: Rel. humidity Delta
Communication protocol: All
Description: Specifies by how much the relative humidity value must change in absolute terms compared to the last transmission for an ALARM transmission to be triggered. This transmission is carried out independently of the normal transmission interval.
Key (NFC Parameters): hdt
Modul: Sentiface
Group: 0x05
Property ID: 0x01
Preset value:
Minimum adjustable value: 5
Maximum adjustable value: 100
Unit:
read/write: rw
Module key: 1111
Name: Rel. humidity yellow alarm
Communication protocol: All
Description: Specifies the relative humidity threshold in ppm that must be exceeded for the sensor to change to the yellow state (yellow LED lights up).
Key (NFC Parameters): hyt
Modul: Sentiface
Group: 0x05
Property ID: 0x02
Preset value:
Minimum adjustable value: 10
Maximum adjustable value: 100
Unit:
read/write: rw
Module key: 1111
Name: Rel. humidity red alarm
Communication protocol: All
Description: Specifies the relative humidity threshold in ppm that must be exceeded for the sensor to switch to the red state (red LED lights up).
Key (NFC Parameters): hrt
Modul: Sentiface
Group: 0x05
Property ID: 0x03
Preset value:
Minimum adjustable value: 10
Maximum adjustable value: 100
Unit:
read/write: rw
Module key: 1111
Name: Rel. humidity Hysteria
Communication protocol: All
Description: Determines the absolute hysteresis in ppm for state changes. If the CO2 concentration falls below a threshold value minus hysteresis, the system switches from a higher to a lower alarm status.
Key (NFC Parameters): hlh
Modul: Sentiface
Group: 0x05
Property ID: 0x04
Preset value:
Minimum adjustable value: 0
Maximum adjustable value: 300
Unit:
read/write: rw
Module key: 1111
Group SCW Alarms
Name: Temperature Offset
Communication protocol: All
Key (NFC Parameters): tto
Group: 0x06
Property ID: 0x00
Preset value:
Minimum adjustable value: -5
Maximum adjustable value: 5
Unit:
read/write: rw
Name: Temperature Target Emission
Communication protocol: All
Key (NFC Parameters): tte
Group: 0x06
Property ID: 0x01
Preset value:
Minimum adjustable value: 0
Maximum adjustable value: 100
Unit: %
read/write: rw
Group SCW Calibration
Name: Autocalibration
Communication protocol: All
Key (NFC Parameter): tto
Group: 0x06
Property ID: 0x00
Preset value:
Minimum adjustable value: -5
Maximum adjustable value: 5
Unit:
read/write: rw
Name: Autocalibration
Communication protocol: All
Key (NFC Parameter): tto
Group: 0x06
Property ID: 0x00
Preset value:
Minimum adjustable value: -5
Maximum adjustable value: 5
Unit:
read/write: rw
Name: Autocalibration
Communication protocol: All
Key (NFC Parameter): tto
Group: 0x06
Property ID: 0x00
Preset value:
Minimum adjustable value: -5
Maximum adjustable value: 5
Unit:
read/write: rw
Name: Autokalibrierung
Communication protocol: All
Key (NFC Parameter): tto
Group: 0x06
Property ID: 0x00
Preset value:
Minimum adjustable value: -5
Maximum adjustable value: 5
Unit:
read/write: rw
Name: Autokalibrierung
Communication protocol: All
Key (NFC Parameter): tto
Group: 0x06
Property ID: 0x00
Preset value:
Minimum adjustable value: -5
Maximum adjustable value: 5
Unit:
read/write: rw
Dokumentationen Links