Skip to content
English
  • There are no suggestions because the search field is empty.

Hyperion Technical Datasheet

Are you looking for a data sheet for Hyperion?

 

 

Hyperion Technical Data Sheet (German) – HTML
📄 You can view the PDF above or download it here .
Hyperion Technisches Datenblatt
Figure 1

Version History

Version Date Revision
1.0.0 February 18, 2025 Creation
1.0.1 March 25, 2026
  • Formatting, Version History

Features

  • mioty® or LoRaWAN® wireless interface (Modbus or WMBUS upon request)
  • Bidirectional meter (supply and consumption)
  • MID B + D approval for billing purposes
  • Environmental conditions Mechanical: M2
  • 1 and 5 A current transformer connection for up to 20,000/5 or 4,000/1 A; the transformer ratio can be configured multiple times via sealable buttons
  • Direct connection up to 100 A
  • 2 or 4 tariffs (configurable on the meter)
  • High-load Opto Power MOSFET
  • S0 pulse output, 5–60 V AC and V DC
  • Graphical LCD display (38x28 mm), with backlight
  • Dynamic 8-digit display with up to three decimal places

MID Approval for Billing Purposes

The Hyperion has been tested and approved in accordance with MID Modules B + D (Measurement Instruments Directive 2004/22/EC of the European Commission).

Display Operation

A 38x28 mm backlit graphic LCD display allows for easy reading of measurement values and settings even under difficult lighting conditions.

The desired menu language can be selected using the buttons. The clear and intuitive operation simplifies commissioning as well as daily work with the energy meters.

Parameters

Total/3 Phases Per phase Per rate
Active energy consumption (kWh)
Active energy supply (kWh)
Reactive energy consumption (kvarh)
Reactive power supply (kvarh)
Active power (kW) -
Reactive power (kvar) -
Apparent power (kVA) -
Current (A) -
Voltage (V) L-N - -
Voltage (V) L-L - -
Power factor (Cos Phi) - -
Frequency (Hz) - -
Number of power outages - -
Load profile storage - -

Features

  • Logbook for metrology-related events and configuration changes
  • Change of time or date
  • Change of current transformer ratio
  • Change of pulse rate and pulse duration
  • Change of voltage transformer ratio
  • Buffered internal clock

The internal clock is backed up in the event of a power failure. The load profile is saved every 15 minutes. The memory can be read via the interface or viewed on the display.

Ordering Information

Model Type Part No.
Hyperion Energy Meter with direct measurement up to 100A LoRaWAN, internal antenna S-HYPE-LOEU-D-INT
Hyperion Energy Meter with direct measurement up to 100A LoRaWAN, external antenna S-HYPE-LOEU-D-EXT
Hyperion Energy Meter with direct measurement up to 100A Mioty, internal antenna S-HYPE-MIOTY-D-INT
Hyperion Energy Meter with direct measurement up to 100A mioty, external antenna S-HYPE-MIOTY-D-EXT
Hyperion Energy Meter with current transformer connection LoRaWAN, internal antenna S-HYPE-LOEU-W-INT
Hyperion Energy Meter with current transformer connection LoRaWAN, external antenna S-HYPE-LOEU-W-EXT
Hyperion Energy Meter with current transformer connection Mioty, internal antenna S-HYPE-MIOTY-W-INT
Hyperion Energy Meter with current transformer connection mioty, external antenna S-HYPE-MIOTY-W-EXT

Wiring diagram 3/100

Anschlussschema 3/100
Figure 2

Wiring diagram 3/5

Anschlussschema 3/5
Figure 3

Product Information

Feature Details
Active energy Class B (1%) according to EN50470-3 Direct-connection meter
Class B (1%) according to EN50470-3 Transformer meter
Reactive energy Class 2 (2%) according to EN62053
Operating voltage L-L: 400 VAC ± 20%
L-N: 230 VAC ± 20%
Maximum current Direct-reading meters: 100 A
Transformer-based meters: 6A
Inrush current Direct-reading meters: 20 mA at power factor 1
Transformer-based meters: 1 mA at power factor 1
Mains frequency Nominal frequency: 50 Hz, 60 Hz on request
Limit frequencies: 40–65 Hz
Self-consumption Voltage path 0.8 VA / 0.8 W per phase
Current path of transformer meter: 0.075 VA per phase
Current and voltage connection Direct-reading meters: 1.5–35 mm², torque: 2 Nm, max. 3 Nm
Transformer meters: 1–6 mm², torque: 0.8 Nm, max. 1 Nm
Tariff switching 2 or 4 tariffs (configurable on the meter), tariff switching: 230 VAC
Current transformer ratios On the Hyperion 3/5, the current transformer ratio can be configured multiple times.
Current transformer /5 A 5/5 A to 20,000/5 A in 5 A increments
Current transformer /1 A 1/1 A to 4,000/1 A in 1 A increments
Display (LCD) Dynamic 8-digit display with up to three decimal places
Graphical backlit LC display (WxH) 38x28 mm
S0 pulse output Standard EN62053-31
Output: Potential-free
Pulse rate per kWh/kVarh: 1, 10, 100, 1,000, or 10,000 pulses
Pulse width: 2 ms, 10 ms, 30 ms, 40 ms, or 120 ms
Pulse rate and length adjustable on the meter
Optional data interfaces LoRa or Mioty (optional SMA connector for external antenna)
Optical (IR) D0 interface EN 62056-21
Data retention Power-off retention in EEPROM, minimum 10 years
Optional: IOTA Tangle (blockchain technology)
Clock Buffered clock (up to 18 days)
Time synchronization via interfaces possible
Mounting / Installation Position-independent
On a 35 mm DIN rail or with front mounting frame
Weight approx. 350 g
Housing Housing material: Polycarbonate, halogen-free, recyclable
Housing protection class IP51, terminal protection class IP20
Protection class II
Dimensions (LxWxD) 90x91x72 mm
5 modules wide
Approvals CE and MID B + D
Suitable for energy management according to ISO 50001
Environmental conditions Mechanical: M2
Electromagnetic: E2
Operating temperature: -25 °C to +70 °C
Storage temperature: -30 °C to +70 °C
Relative humidity: Annual average 75%, short-term 90%, non-condensing
Safety Note Electricity meters may only be installed by a qualified electrician. Current transformers must not be operated with the cover open, as high voltages may occur. These can result in personal injury and/or property damage.
Device Selection To ensure the simplest possible maintenance or replacement (e.g., calibration) of the Hyperion energy meter, the following applies to applications where a simple and cost-effective shutdown of the system is not possible.

Technical Specifications

Feature Value Unit
Dimensions (L × W × D)90 × 91 × 72mm
Width in modules5TE
WeightApprox. 350g
Housing materialPolycarbonate, halogen‑free, recyclable
Terminal protection classIP20
Enclosure protection classIP51
Electrical protection classII
Operating temperature−25 to +70°C
Storage temperature−30 to +70°C
Relative humidityAvg. 75%, short‑term 90% (non‑condensing)%
Mechanical environmentM2
Electromagnetic environmentE2
Display typeGraphic LC with backlight
Display size38 × 28mm
Display resolution8 digits, up to 3 decimal places
ApprovalsCE, MID B + D, PTBA 20.1, PTBA 50.7
Energy management complianceISO 50001
Mounting typeDIN rail (35 mm) or front mounting frame
Mounting orientationPosition‑independent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Documentation Links

You can find the links for further documentation on Hyperion Energy Meter here : 

 

 

Specifications subject to change without notice. All information provided without guarantee.