Juno mioty® TH TILT –NFC & Downlink Description

Are you looking for the Juno mioty® TH TILT  NFC and downlink description

📄 You can view the PDF above or download it here .

Table of Contents

1. Version History

VersionDateRevision
1.0.0April 30, 2026Created

2. Module Overview

ModuleModule KeyGroupGroup IDDescription
Sentiface0x1XXXTimings0x00Defines parameters for measurements and transmission behavior
Sentiface0x1XXXAlarms and thresholds0x01Defines alarms and limit values, such as upper and lower temperature limits
Sentiface0x1XXXSettings for opening detection0x02Defines measurement thresholds for triggering the alarm for temperature and relative humidity
Sentiface0x1XXXSettings for tilt detection0x03Defines the behavior of the accelerometer

Tables for cross-product modules (Senticom/Sentivisor) can be found in the Generic NFC and Downlink documentation.

For more information on configuring sensor communication, refer to the respective mioty® documentation depending on the version.

Instructions valid for versions:

Item CodeIFM Article CodeFeatures
S-JUNO-IX-MIOTY-THZJF 201INDUSTRIAL JUNO IP67 TH Sensor, Temperature and Relative Humidity with Tilt Detection and Door Open Detection mioty®

3. Sentiface: Timings Group 0x00

ResourcesResource IDDescriptionKey (NFC/BLE)MinMaxFactory SettingUnitModule Key
MEASUREMENT PERIOD0x00Specifies the interval at which measurements are taken. 5 minutes means that the sensor takes a measurement every 5 minutes.period136030min1111
REGULAR TRANSMISSION INTERVAL0x01Number of measurements performed prior to transmission.every1646
1111

4. Sentiface: Alarm Settings Group 0x01

ResourcesResource IDDescriptionKey (NFC/BLE)MinMaxFactory SettingUnitModule Key
ALARM ACTIVE0x00Indicates which alarms, whether for temperature or relative humidity, are active:
0: Both alarms deactivated
1: Temperature alarm active
2: Relative humidity alarm active
3: Both alarms active
aact031
1111
TEMPERATURE DELTA0x01Specifies the absolute change in temperature compared to the last transmission that must occur to trigger an ALARM transmission. This transmission is performed independently of the normal transmission interval.tdt1505°C1111
UPPER TEMPERATURE LIMIT0x02Specifies the upper absolute limit at which an alarm is triggered.tht08540°C1111
TEMPERATURE BELOW LIMIT0x03Specifies the lower absolute limit at which an alarm is triggered.tlt-25750°C1111
RELATIVE HUMIDITY DELTA0x04Specifies the absolute change in relative humidity compared to the last transmission that must occur in order to trigger an ALARM transmission. This transmission is performed independently of the normal transmission interval.hdt18020%RH1111
RELATIVE HUMIDITY UPPER LIMIT0x05Specifies the upper absolute limit at which an alarm is triggered.hht510080%RH1111
RELATIVE HUMIDITY BELOW THRESHOLD0x06Specifies the lower absolute limit at which an alarm is triggered.hlt09520%RH1111
TEMPERATURE HYSTERESIS0x07Determines the absolute hysteresis in °C during state changes. If the temperature falls below or exceeds a threshold value minus the hysteresis, the system switches from a higher to a lower alarm state.thy0102°C1111
HYSTERESIS REL. HUMIDITY0x08Determines the absolute hysteresis in %RH during state changes. If the relative humidity falls below or exceeds a threshold value minus the hysteresis, the system switches from a higher to a lower alarm state.hhy0305%RH1111

5. Sentiface: Opening Detection Group 0x02

PropertyProperty IDDescriptionKey (NFC/BLE)MinMaxDefaultUnitModule Key
OPENING COOLDOWN0x00Specifies a time period during which, after an opening has been triggered, another opening cannot be triggered (de-bounces the openings).acool06000sec1111
OPENING TIME ALARM0x01Specifies how long the lid must remain open before an alarm is triggered (0 = immediate alarm).oaaf028800sec1111
OPENING MODE0x02Describes which direction the sensor faces when closed and which angles are set for opening detection. Settings 0–7 use the accelerometer; 8 and 9 use the Hall sensor:
0: off
1: Ultra Low Power. Fixed threshold 50°. Closed when facing down (Face Down).
2: Ultra Low Power. Fixed threshold 50°. Closed when facing up (Face Up).
3: Ultra Low Power. Fixed threshold 50°. Closed when facing sideways.
4: Advanced tilt sensing. Adjustable threshold. Closed when facing down (Face Down).
5: Advanced tilt sensing. Adjustable threshold. Closed when facing up (Face Up).
6: Advanced tilt sensing. Adjustable threshold. Closed when facing sideways.
7: Advanced tilt sensing. Adjustable threshold. Automatic calibration of closed orientation.
8: Container is closed when the magnet is in contact.
9: Container is open when magnet is present.
opmo091
1111

6. Sentiface: Advanced Tilt Settings Group 0x03

PropertyProperty IDDescriptionKey (NFC/BLE)MinMaxDefaultUnitModule Key
SAMPLING PERIOD0x00Specifies how often the accelerometer determines the angle. The higher the frequency, the higher the power consumption.tspe26002s1111
TRIGGER LEVEL0x01Specifies the angle at which an opening is detected or an alarm is triggered.ttle518020°1111
TRIGGER HYSTERESIS0x02Hysteresis value for the opening angle.tthy1904°1111

7. Example Downlinks

SettingDownlink
period = 1000 11 11 00 00 00 00 00 0A
every = 500 11 11 00 01 00 00 00 05
alarm_act = 000 11 11 01 00 00 00 00 00
mioty CE and WEEE compliance marks