LIO-Aion Settings and Downlink Description
Are you looking for LIO-Aion Settings and Downlink Description?
📄 You can view the PDF above or
download it here
.
1. Configuration Overview
| Property | Value |
|---|---|
| Product | AION LIO IO-Link Adapter |
| Communication | IO-Link Master with LPWAN Connection |
| Configurable Groups | Timing, Trigger, IO-Link Telemetry |
| Measurement Interval | 1 to 660 minutes |
| Keep-Alive Interval | 1 to 24 measurements |
| Measurement Trigger | Local or uplink-controlled |
2. AION Resource Groups
| Module | Group | Group ID | Description |
|---|---|---|---|
| AION | Timing | 0x00 | Measurement interval and keep-alive uplink interval |
| AION | Trigger | 0x01 | Manual measurement trigger |
| AION | IO-Link Telemetry | 0x02 | Read-only IO-Link device identity and process data |
3. Kconfig Parameters
| Symbol | Type | Default | Description |
|---|---|---|---|
| CONFIG_SENTOS_MODULE_AION | bool | n | Enables the AION module |
| CONFIG_SENTOS_AION_INTERFACE_IO_LINK | bool | off | Enables the IO-Link master variant with one port |
| CONFIG_SENTOS_AION_IO_LINK_STARTUP_TIMEOUT_MS | integer | 5000 ms | Wait time for the first valid process data sample |
4. Timing Group (0x00)
| Resource | ID | Key | Min | Max | Default | Unit |
|---|---|---|---|---|---|---|
| Measurement Period | 0x00 | period | 1 | 660 | 5 | minutes |
| Regular Transmission Interval | 0x01 | every | 1 | 24 | 1 | measurements |
5. Trigger Group (0x01)
| Resource | ID | Description | Input |
|---|---|---|---|
| Trigger measurement | 0x01 | 0x0001 triggers an immediate measurement and sends the data via uplink. Any other two-byte value merely starts a local measurement. | 2-byte big-endian |
6. Technical Notes
- The measurement interval can be configured between 1 and 660 minutes.
- The keep-alive uplink interval is defined as the number of measurements.
- The IO-Link startup timeout can be configured between 1000 ms and 30000 ms.
- The "IO-Link Telemetry" group provides the device identity and raw process data.
- The trigger function supports remote triggering of measurements via a big-endian command value.
- All IO-Link process data is provided by the integrated AION LIO IO-Link master.
© Sentinum GmbH - All rights reserved.
All content in this document, including text, tables, and images, is protected by copyright and is the property of Sentinum GmbH.
Unless otherwise stated, all images are subject to the copyright of Sentinum GmbH.
Reproduction, distribution, or use, even in part, is not permitted without express written permission.
Subject to technical changes. All information is provided without warranty.